Polyurethane Foaming Industry
Case Introduction
DOCO Constant Temperature Cold and Hot Water Machine applied to polyurethane foaming industry for customer Penglai Zhonghui
![]() |
![]() |
Model Item | DC-CH1A | DC-CH2A | DC-CH3A | DC-CH5A | DC-CH8A- D | DC-CH10A-D | DC-CH15A-T | DC-CH20A-F | |
Horsepower | HP | 1 | 2 | 3 | 5 | 8 | 10 | 15 | 20 |
Refrigerating Capacity | kcal/h | 2390 | 4730 | 7086 | 11610 | 18060 | 23220 | 35260 | 46440 |
KW | 2.78 | 5.5 | 8.24 | 13.5 | 21 | 27 | 41 | 54 | |
Temperature Control Range℃ | 5-25℃ | ||||||||
Power Supply | 220V 50HZ 1PH | 380V 50HZ 3PH | |||||||
Compressor Power (kw) | 0.83 | 1.7 | 2.5 | 4 | 3*2 | 4*2 | 4*3 | 4*4 | |
Refrigerant | R22 ( R407、R410 Environmental Refrigerants are optional ) | ||||||||
Condenser | Type |
Air cooled condenser(corrugated open-window aluminum foil radiating fin with copper tube inside,20% increase in heat dissipation efficiency) |
|||||||
Fan | Type | Large-flow and Low-Noise Axial Fan Motor | |||||||
Evaporator | Type |
Coil evaporator inside water tank(stainless steel plate heat exchanger or shell-tube dry evaporator are optional) |
|||||||
water tank volume L |
20 | 35 | 50 | 62 | 125 | 125 | 240 | 300 | |
Electric Heater | Power KW | 3 | 6 | 9 | 12 | 15 | 18 | 24 | 36 |
Chilling Water Pump | Power KW | 0.37 | 0.37 | 0.37 | 0.37 | 0.75 | 0.75 | 1.5 | 1.5 |
chilling water flow m³/h | 0.6-0.8 | 0.9-1.3 | 1.3-1.8 | 2.6-3.5 | 4.2-5 | 5.1-6 | 7.5-9 | 10-12 | |
Chilling Water Inlet/outlet Caliber |
1/2" | 1/2" | 1/2" | 1" | 1-1/2" | 1-1/2" | 2" | 2" | |
Dimensions | Length mm | 604 | 775 | 925 | 1155 | 1600 | 1600 | 1710 | 1820 |
Width mm | 484 | 555 | 575 | 655 | 805 | 805 | 850 | 1050 | |
Height mm | 876 | 908 | 1012 | 1082 | 1355 | 1355 | 2100 | 2100 | |
Safety Protections | Delay protection, flow protection, compressor overheating protection, refrigerant high and low pressure protection, overcurrent protection, phase sequence / phase deficiency protection, overload protection, overtemperature protection, etc. |
Technical Specifications:
1. Model number specification: e.g. DC-CH10A-D, “DC” indicates Doco company code, “CH” indicates constant temperature cold and hot water machine, “10” indicates 10 horsepower, “D” indicates dual system with two compressors, “T” indicates three compressors, “F” indicates four compressors.
2. *Compressor power: *2indicates two compressors working and two independent refrigerating systems.
3. Refrigerating capacity parameter basis: the temperature of inlet and outlet chilled water is 12℃/ 7 ℃ and the
temperature of inlet and outlet cooling air is 30℃ / 35℃.
4. Working ranges: the temperature range of chilling water is from 5℃ to 40℃, the temperature difference between inlet and outlet chilling water is from 3℃ to 8℃, the ambient temperature can not be higher than 40℃, and the high- temperature model should be selected when the ambient temperature is higher than 40℃.
5. We reserve the right to revise the above information without prior notice.